detcon inc.Model 1010SS-N4XNEMA 4X Stainless Steel Control EnclosureP.N. 954-101051-101P.O. 4500645366Operator’s Installation & Instruction Manual
Table of Contents1.0 Introduction1.1 Description1.2 Specifications1.3 Battery Backup - Low Voltage Cutoff System1.4 Relay Logic Description1.5 Install
1.0 INTRODUCTIONThe Detcon Model 1010SS-N4X consists of 3 major assemblies:• The NEMA 4X (304 stainless steel) control enclosure.• The Model 10 singl
Model 1010SS-N4X NEMA 4X Control Enclosure PG.4OutputsDiscrete Analog 4-20 mA DC - Not currently usedSerial RS-485 Modbus™ - Not currently usedDisc
1.4 RELAY LOGIC DESCRIPTIONRelay Assignments (Refer to Drawing #4146, 3 of 3, for Relay Layout)K1 - Discrete warning relay for channel 1K2 - Discrete
1.5 INSTALLATION1. Securely mount the 1010SS-N4X enclosure in accordance with the drawing in Figure 2.NNoottee:: Reference Drawing #4120 for wiring t
1.6 START UPUpon completion of all field wiring per Figure 3 below, depress the top of the circuit breaker switch located on thefront panel. Be sure
1.8 SPARE PARTS LISTRefer to Saudi Aramco SPDP document for a completet list of spare parts.1.9 WARRANTYDetcon Inc., as manufacturer, warrants under