4.0 SPECIFICATIONS
Method of Detection
Catalytic detector diffusion/adsorption
M
easurement Range
0-100% LEL (lower explosive limit)
Accuracy/Repeatability
± 3% LEL in 0-50% LEL Range
± 5% LEL in 51-100% LEL Range
Response/Clearing Time
T50 <10 seconds; T90 <30 seconds
Zero Drift
< 5% per year
Operating Temperature Range
-40° to +167° F; -40° to +75°C
Operating Humidity Range
0-100% RH (non-condensing)
Output
Linear 4-20 mA DC
Input Voltage
11.5-28 VDC
Power Consumption (maximum)
< 2.1 watts @ 24 VDC
Electrical Classification
Explosion Proof; Class I, Div. 1; Groups B, C, D
Safety Approvals
CSA/NRTL (US OSHA Certified)
Warranty
Sensor: 2 year conditional
Transmitter: 2 year
Field Wiring
3 conductor; max 10 ohms single conductor resistance
Max Ohms Between Sensor and Transmitter (in applications where sensor head is remotely mounted)
1/2 ohm
5.0 INSTALLATION
Optimum performance of ambient air/gas sensor devices is directly relative to proper application and
installation practice.
5.1 Field Wiring Table
Detcon Model FP-424C wiring consists of three conductors: + (+24VDC power), – (DC common), and MA
(4-20 mA DC signal output referenced to DC common). Maximum single conductor resistance between
sensor and controller is 10 ohms. Maximum wire size for termination in the sensor assembly terminal con-
nector board is 14 gauge. Note the wiring table below.
AWG Meters Feet
20 240 800
18 360 1200
16 600 2000
14 900 3000
Note 1:
This wiring table is based on stranded tinned copper wire and is designed to serve as a reference only.
Note 2: Shielded cable may be required in installations where cable trays or conduit runs include high volt-
age lines or other sources of induced interference.
Note 3: The supply of power must be from an isolating source with over-current protection as follows:
AWG Over-current Protection AWG Over-current Protection
22 3A 16 10A
20 5A 14 20A
18 7A 12 25A
Detcon Model FP-424C Combustible Gas Sensor PG.7