detcon inc.
Detcon MicroSafe
TP-524C Hydrogen Sulfide Sensor
This manual covers the following ranges: 0-20 PPM, 0-50 PPM, and 0-100 PPM
Operators Installation & Instruction Manual
May 09, 2012 • Document #2297 • Version 2.5
Vista de pagina 0
1 2 3 4 5 6 ... 19 20

Indice de contenidos

Pagina 1 - Detcon MicroSafe

detcon inc.Detcon MicroSafe™TP-524C Hydrogen Sulfide SensorThis manual covers the following ranges: 0-20 PPM, 0-50 PPM, and 0-100 PPMOperator’s Insta

Pagina 2 - Table of Contents

cult to access. Such a location creates problems for maintenance and calibration activities. Detcon provides the TP-524C sensor in a remote-mount conf

Pagina 3 - 3.0 DESCRIPTION

3.6.2 Remote Mount Heater Voltage SetupIf the sensor has been installed using the remote mounting configuration as described in section 3.5.6, the sen

Pagina 4 - Base Connector Board

A magnetic programming tool (see figure 5) is used to operate the switches. Switch action is defined as momentarycontact, 3 second hold, and 15 second

Pagina 5 - Functional

The “Set X Value” menu is used for adjustments of the linearization coefficient. This is a factory authorized adjust-ment. The default setting is “6.0

Pagina 6 - 3.4 OPERATING SOFTWARE

f) Enter the calibration span menu by holding the programming magnet stationary over “PGM 1” for 3 secondsThe display will read “1-SPAN 2-EXIT” Hold

Pagina 7 - 3.4.3.1 Program Status

The following procedure is used to view the programming status of the sensor:a) First, enter the programming menu by holding the programming magnet st

Pagina 8 - Figure #2

System FaultIf the detector has an irrecoverable calculation error, the display will indicate: “SYSTEM FAULT”.Memory FaultIf new data points cannot su

Pagina 9 - TP-524C-RS

Poor calibration Repeatability1. Check for adequate Sensor Life.2. Check Heater Voltage Setting (should be 5.25 V).3. Use humidifier filled with Disti

Pagina 10 - Material Requirements

3.13 WARRANTYDetcon, Inc., as manufacturer, warrants each hydrogen sulfide sensor element (PN 399-800000-000), for a ten yearperiod under the conditi

Pagina 11 - Figure #6

3.15 SOFTWARE FLOW CHART3.16 REVISION LOGDetcon Model TP-524C Hydrogen Sulfide SensorPG.19NORMALOPERATIONPGM1 (M) PGM2 (M)PGM1 (3)INCDECPGM1 (3) PGM2

Pagina 12

Table of Contents3.0 Description3.1 Principle of Operation3.2 Application3.3 Specifications3.4 Operating Software3.5 Installation3.6 Start-up3.7 Calib

Pagina 13

Detcon Model TP-524C Hydrogen Sulfide SensorPG.20

Pagina 14 - Additional Notes

3.0 DESCRIPTIONDetcon MicroSafe™ Model TP-524C, hydrogen sulfide sensors are non-intrusive “Smart” sensors designed to detectand monitor H2S in air.

Pagina 15 - 3.9 PROGRAM FEATURES

3.0.2 Microprocessor Control CircuitThe control circuit is microprocessor based and is packaged as a plug-in field replaceable module, facilitating e

Pagina 16 - Memory Fault

The sensors are packaged in a cast metal explosion proof enclosure. The enclosure is fitted with a threaded coverthat has a glass lens window. Magneti

Pagina 17 - 3.12 SPARE PARTS LIST

3.3 SPECIFICATIONSMethod of DetectionSolid state metal oxide diffusion/adsorptionElectrical ClassificationCSA-NRTL (US OSHA) approved Class I; Groups

Pagina 18 - Terms & Conditions

Calibration mode allows for sensor span adjustments. Unless otherwise specified, span adjustment is performed at10 ppm H2S in air for the range 0-20 p

Pagina 19 - EVISION LOG

3.5.2 Sensor LocationSelection of sensor location is critical to the overall safe performance of the product. Five factors play an importantrole in s

Pagina 20

Maintenance AccessConsideration should be given to easy access by maintenance personnel as well as the consequences of close prox-imity to contaminant