
Model FP-524D-HRT
FP-524D-HRT Instruction Manual Rev. 0.1 Page 46 of 48
1000 ohms maximum loop load @ 24VDC
0mA All Fault Diagnostics
2mA In-Calibration
4-20mA 0-100% full-scale
22mA Over-range condition
HART Version 7.0
Manufacture ID 0x6007
Device ID 0xE08B
Status Indicators: 4-digit LED Display with gas concentration, full-script menu
Prompts for AutoSpan, AutoZero, Set-up Options, and Fault Reporting
Faults Monitored: Loop Fault, Input Voltage Fault, Zero Fault, Sensor Fault,
Processor Fault, Memory Fault, Calibration Fault(s)
Cable Requirements: Power/Analog: 3-wire shielded cable
Maximum distance is 13,300 feet with 14 AWG
Mechanical Specifications
Length: 5 inches (200mm), including Splashguard
Width: 6 inches (140mm)
Weight: 2.7lbs (3.4Kg)
Mechanical Connection: ¾” Male NPT threaded connection
Electrical Connection: three 14 gauge (maximum) wire terminal landings
Comentarios a estos manuales