Sentinel CX
Sentinel CX Sensor Station IM Rev. 1.2 Page 6 of 6
1.7 Alarm Outputs
The SmartWireless® CXT can optionally include an internal Relay PCA for activating alarm annunciators.
The Relay PCA includes four Class I Division II relays rated for 10A @ 30VDC/250VAC. If the
SmartWireless® CXT includes an attached strobe and/or horn, these devices are also activated by the Relay
PCA.
Each Relay PCA must have a unique Modbus address. The Relay PCA includes a single rotary switch to set
its Modbus address (Figure 5). The most significant digit of the address is hard-wired to “8”. The least
significant digit (LSD) is controlled by the rotary switch. The Relay PCA addresses should start at 80h and
continue sequentially for each SmartWireless® CXT in the system.
Internal Alarm
Connections
Modbus
Connections
Alarm Relay Connections
Modbus
LSD Address
Figure 5 Relay PCA
If the Smart Wireless® CXT is ordered with the Relay PCA option, the Relay PCA can be configured to
provide either ‘Wet’ or ‘Dry contacts for external annunciator activation. The ‘Wet’ contact option
provides 12V Battery Power to external annunciators when an alarm is initiated. The ‘Wet’ contacts are
available on a 5 pin Alarm Connector (Figure 6). These outputs are specifically meant for external 12V
annunciators such as the external A1 C1D2 Horn, which is designed to operate on the unit’s 12V Battery.
12V Battery Power
12V Return
Relay PCA
NC
COM
NO
FAULT
NC
COM
NO
ALARM 3
NC
COM
NO
ALARM 2
NC
COM
NO
ALARM 1
Enclosure
ALARM 2 (Gray) 3
Alarm Connector
ALARM 3 (Brown) 4
FAULT (BLUE) 5
ALARM 1 (White) 2
GND (Black) 1
1
1
2
3
4
5
Figure 6 External Alarm Connector pin out for ‘Wet’ alarm contacts