Sentinel CX
Sentinel CX Sensor Station IM Rev. 1.2 Page 5 of 5
Modbus Address
LSD Switch
Modbus Address
MSD Switch
Figure 3 Sensor Input PCA
Four "quick connects" on the side of the CXT are for sensor connection (Figure 4), supply power to the
sensor from the internal battery and accept the 4-20mA signal from the sensor.
NOTE
Power supplied to the sensors is 11VDC. Any attached sensor must be designed to work at
this voltage level.
The four sensor input lines are fused at the PC board level for safety purposes. These fuses are not
designed for field replacement and shall not under any circumstances be attempted to be changed out by
anyone but Detcon Factory trained Service personnel.
CAUTION
These PC board mounted fuses are not designed for field replacement and shall not
under any circumstances be attempted to be changed out by anyone but Detcon
Factory-Trained Service personnel.
4-20mA (Grn/Ylw) 4
GND (Blue) 2
PWR (Brown) 1
Cable to Sensor 1
Sensor Connector
Shld (Gray) 3
(Grn/Ylw) 4-20mA
(Brown) PWR
(Blue) GND
Shld
Sensor
1
1
PCB
Enclosure
Pin 1
Figure 4 Sensor Input Connector Pin-out