4. RS-485 Modbus
TM
Protocol
Model FP-624D-HT sensors feature Modbus™ compatible communications protocol output and are
addressable via the program mode. Communication is via a two wire, half duplex RS-485, 9600 baud, 8 data
bits, 1 stop bit, no parity, with the sensor set up as a slave device. A master controller up to 4000 feet away
can poll up to 256 different FP-624D-HT sensors. This number may not be realistic in harsh environments
where noise and/or wiring conditions would make it impractical to place so many devices on the same pair of
wires. If a multi-point system is being utilized, each sensor should be set for a different address. Typical
address settings are: 01, 02, 03, 04, 05, 06, 07, 08, 09, 0A, 0B, 0C, 0D, 0E, 0F, 10, 11…etc.
Sensor Serial ID numbers are factory default to 01. These can be changed in the field via the Operator
Interface described in Section 3.5.8.
The following table explains the details of the Modbus™ protocol that the FP-624D-HT sensor supports.
Table 3 Modbus Registers
Modbus Register
FC REG Content Description R/W Content Definition
Value Meaning Range
06 40001 Write Detectable Range 10000 For 0-10000
FP – Read only
TP – 20, 50, 100, 200
PI – 0 to 10000
03 40002
Read Concentration
3,2
R 1000 Bound by range. If > range, this
value is in fault.
5% to 95% of Range (40001)
TP – 2% to 50% of Range (40001)
IR – 5% to 95% of Range (40001)
PI – 1% to 95% of Range (40001)
03 40004 Read Sensor Life R 85 For 85% sensor life
0x0004 Temperature Fault
0x0080 Clearing Fault
0x0400 Sensor Fault
0x2000 <reserved>
0x4000 In Calibration
0x8000 Communication Error
03 40006 Read Model # R 1, 2, 3, 4, 5
DM, FP, IR, TP, PID
respectively
03 40007 Read Days Since Cal R 29 29days
03 40008
4-20 Current Output
R 400 4.00mA
03 40009
Read Input Voltage
R 2400 24.00V
03 40010 Read Temperature R 28 28 °C
03/
40011 Special #1 R/W
Function Dependant on Value
of 40006 (See Special Register
FC REG Content Description R/W Content Definition
Value Meaning Range
Function Dependant on Value
of 40006 (See Special Register
Table)
03 40013 Special #3 R
Function Dependant on Value
of 40006 (See Special Register
Table)